| Meter Mounted, Frequency to Analog Converter, FIP |
 |
The FIP is a microprocessor based, meter
mounted, analog output sensor. Each unit has a sensor, amplifier and
converter module built into an Adalet housing. The FIP is designed to
handle frequencies up to 2,000 Hz. The operational frequency range is user
defined via four BCD rotary switches, where the high flow rate in
frequency is set to 20 mA, 5V or 10V, and the output signal is
automatically scaled. End connection options include ½” N.P.T. for
running conduit pipe into hazardous locations, or a 3-pin electrical
connector. |
|
Technical Specifications
-
Supply Voltage: (Vcc) 10-30 VDC
-
Supply Current: 60mA max
-
Signal Output: 0-20mA, 4-20mA or, 0-5V, 0-10V, 1-5V,
2-10V
-
Max. Load Impedance: (Vcc/0.02) - 275 ohm (for mA out)
-
Min. Load Impedance: 500 ohm (for Volt out)
-
Driving Capacity For voltage output only: 10 mA max.
-
Temperature Range: 0-185°F
-
Jumper Settings J1:
AB-Analog Output, BC-Frequency Output
-
Jumper Settings J2: AB-Housing Ground, CB-Signal
Ground
-
Response Time: 1/F + 25 msec
-
Frequency Input: 2 KHz max.
-
Diagnostics: A glowing LED indicates the unit is
working. The LED will blink to show an active frequency.
|
 |
|
|